Đóng

19/02/2021

Đầu báo nhiệt

IP 101-29-PR prot.R3

Analogue addressable maximum differential thermal detector IP 101-29 PR prot. R3 is designed to detect fires accompanied by temperature increase inside the space under monitoring in closed rooms of various buildings and structures as well as to transmit a “Fire” signal to receiving and control device Rubezh-2OP prot.R3.

Power supply from DCL (28 – 36 V)
Detector trip temperature from 54 to 70 °С
LED flashing frequency in stand-by / “Fire” mode 0,2 Hz/2 Hz
Overall dimensions of the detector with power outlet, no more than Ø94 × 58 mm
Detector weight, power outlet including, no more than 120 g
Operating temperature range from -25 to +55°С
Average service life, at least 10 years

The detector represents temperature direct measuring device with two ways of fire detection: by maximum temperature and by rate of temperature rise.

The detector performs the following functions:

  • ambient temperature measuring;
  • temperature change rate calculation;
  • measuring results processing using special algorithms and “Fire” signal transmission to receiving and control device;
  • indication of detector operation mode;
  • functioning test with a button or an optical tester OT-1.

Power supply and data exchange of the detector is performed via a two-wire DCL.

The detector does not respond to humidity changes and to the presence of flame and natural or artificial light.

The detachable connection between the sensor and the socket provides easy installation, mounting, and maintenance of the detector.

Circular contacts allow easy mounting of the detector without orientation with respect to the socket.

To facilitate DCL shielded cables installation, cable-mounting plate is provided on the power outlet (option).

It can be mounted on dropped ceiling using a special socket combined with mounting rings.