AGS-8/1

Fire Extinguishing Aerosol Generator AGS-8/1

ags-81-1Designed for generating gas-aerosol mixture at concentrations required to extinguish a fire.

Recommended to use fire-extinguishing systems for premises of average volumes.

 

 

  • ags-81-2

    The generator consists of a cylinder with a metal case, which is located at the end of the nozzle cover. The AGS-8/1 is almost identical to the AGS-7/1,but due to labyrinth cooling system, the aerosol and air begins to mix, which significantly reduces the temperature of the gas-aerosol spray.

    Principle of operation:

    By applying an electrical or thermal pulse on node startup, a solid aerosol charge is ignited. Products of combustion pass through the nozzle on the cover of the generator, and the aerosol enters the designated area.

    Manufacturer’s warranty:

    The manufacturer guarantees the generator to the technical requirements and Russian standards if the consumer follows the conditions specified in the instruction manual.

    The warranty period for the generator – 18 months.

    Exploitation period – 5 years.

    Service period – 10 years.

    Certificate (AGS-8/1, AGS-8/2)

    Certificate (AGS-8/1,AGS-8/2)

    Instruction manual

  • Maximum protected volume conditionally sealed room
    (d * <0,001 m-1)
    60m3
    Curb weight of the generator 11.5 kg
    Weight of the aerosol charge 3.4 kg
    Working time 60
    Dimensions
    Width 270 mm
    Length 222 mm
    Height 300
    Activation starter BP-7.5-7.5 VRTH VEE, VELTH
    Resistance of the activation starter 7.5 ± 0.8 ohm 2.5 – 4 ohms
    Minimum start-up current 0.4 А
    Starting voltage 12-24 1.5 – 24
    The duration of the trigger pulse not less than 1.5 sec not less than 0.1 sec
    The inertia of the generator start <1.5 sec
    Operating Conditions
    Operating Temperature Range ± 50 °С.
    relative humidity at 25 ° C. 98%
    mechanical influences (in the frequency range up to 100 Hz) 0,5g
    Classes of fire-fighting