Designed for generating gas-aerosol mixture at concentrations required to extinguish a fire.
Recommended to use fire-extinguishing systems for premises of average volumes.
-
Maximum protected volume conditionally sealed room
(d * <0,001 m-1)60m3 Curb weight of the generator 11.5 kg Weight of the aerosol charge 3.4 kg Working time 60 Dimensions Width 270 mm Length 222 mm Height 300 Activation starter BP-7.5-7.5 VRTH VEE, VELTH Resistance of the activation starter 7.5 ± 0.8 ohm 2.5 – 4 ohms Minimum start-up current 1А 0.4 А Starting voltage 12-24 1.5 – 24 The duration of the trigger pulse not less than 1.5 sec not less than 0.1 sec The inertia of the generator start <1.5 sec Operating Conditions Operating Temperature Range ± 50 °С. relative humidity at 25 ° C. 98% mechanical influences (in the frequency range up to 100 Hz) 0,5g Classes of fire-fighting -